Installation Guidelines for Stationary Compactors

The information contained below is a simplified interpretation of parts of the American National Standard Institute, ANSI-Z245.2-1997, Safety Standards for Stationary Compactors. A copy of this standard is available upon request and should be the primary reference for all safety issues.

Mark-Costello supplies this information only as an aid for understanding the installation section of the standard. Mark-Costello assumes no responsibility for any errors or omissions concerning this material. If you have any questions about the operation or installation of a Mark-Costello compactor, please contact our Customer Service Department at 1-(562) 630-7950

Ground Feed Installation

If the charge box can be reached by the operator…

↓ then

Totally enclosed Hopper (doghouse) with Interlock Switch (mandatory)

↓ or

Sustained Manual Pressure Control (“hold-to-run” button) (mandatory)

↓ or

Special Extended Hopper (as shown above) (mandatory)

Thru-The-Wall Installation

ANSI 2

If the bottom of a thru-the-wall Security Door is not 42″ high

↓ then

Interlock Switch

↓ or

Sustained Manual Pressure Control (“hold-to-run” button)

Note: Interlock Switch is recommended for all Security Doors and is required in some states.

Dock Installation

ANSI 3

If the is no 42″ high barrier between the operator and the charge box

↓ then

Access Gate with Interlock Switch (mandatory)

↓ or

Sustained Manual Pressure Control (“hold-to-run” button) (mandatory)

↓ or

Special Extended Hopper (as shown above) (mandatory)

Walk-On / Drive-On Installation

ANSI 3

If the operator must drive onto the compactor

↓ then

↓ And

Rear Feed Hopper (3 sided) with Access Gate with Interlock Switch (mandatory)

↓ or

Sustained Manual Pressure Control (“hold-to-run” button) (mandatory)

↓ or

Rear Feed Hopper (4 sided) (mandatory)

↓ And

700# Treadplate (mandatory) with Hand & Toe Rails (mandatory)

↓ or

8000# Treadplate (mandatory) with Hand & Toe Rails (mandatory)

↓ And

Must be extended if compactor is not against dock (as shown above) (mandatory)

Cart Dumper Installation

ANSI 5

If the dumper is installed with a compactor

↓ then

Sustained Manual Pressure Control (“hold-to-run” button) (mandatory)

↓ And

Controls located outside area of operation (mandatory)

↓ And

Controls located in sight of area of operation (mandatory)

Note: Interlock Switch is recommended for all Security Doors and is required in some states.

ANSI 6

Location of Emergency Stop

Stop Button must be located within three (3) feet (36 inches) of the Material Feed Area.

Note: Compactor must have Key Switch or other security device.

ANSI 7

Location of Fused Disconnect

An Electrical Disconnect must be located within 50 feet, and in sight of, the Compactor Control Panel.

 

ANSI 8

Hand & Toe Rail Design

Guard Railings for docks with walk-on ramps shall be located around the charging chamber opening. Guard railings and toe boards shall be provided on the sides of all walk-on ramps (in accordance with OSHA 1910.23).

ANSI 9

Installer Labeling Requirements

A Label shall be affixed to the equipment.